Showing posts with label electaical machines. Show all posts
Showing posts with label electaical machines. Show all posts

Monday, April 18, 2011

Induction Machines-Performance

Induction Machines-Performance

  • In induction motor, the magnetizing current is much larger than the active current, so that the no-load power factor is low,0.1 or 0.25
  • If a load torque applied to the shaft, the active component of stator current increases and magnetizing current remains constant, the power factor is raised
  • The maximum effieciency ocurs roughly where the I2R losses in stator and rotor sum to ana amount equal to the no-load constant losses.
  • Usual reltio to maximum to full load torque is 2:1
  • Cage motors:
  • Motors with normal starting torque and current , having cages with low resistance and reactance, low full load slip, good efficiency and power factor
  • Motors with high starting torque and low starting current, using deep-bar rotor or double cage rotors.
  • Motors with high full load slip, using a comparatively high resistance cage , with large starting torque, low starting current and low efficiency. Used for fluctuating torque drives(punching machines)
  • Multispeed Motors:
  • variable-torque, power output proportional to square of speed-fans,centrifugal pumps
  • Constant torque, power output proportional to speed-conveyors,stokers, reciprocating compressors,printing presses
  • Inverse torque, power output rating constant-machine tools,laths,boring mills,drills,planners
  • Gear motors- high speed motors-conveyors,agitators,blowers and screens
  • A startor may either increase rotor resistance or decrease starting current in induction machine
  • The inclusion of rotor resistance will reduce the stator current at standstill and simultaneously raise its power factor.
  • The starting current of a cage motor can only be reduced by lowering the voltage applied to the stator
  • The output and torque for a given slip change as the square of the allied voltage and current reduces in proportionally
  • Direct online startor
  • For direct switching case, if TSC be the torque developed on short circuit at normal voltage with currents ISC then starting torque is TS = TSC and the starting current per phase is IS = ISC the ratio of starting to full load torque is TS/Tn=(ISC/In)2sn
  • Stator resistor startor:
  • The normal voltage per phase to the fraction x is applied to the termianls. The starting current is Is = xIsc and starting torque Ts = x2Tsc
  • The ratio of statig torque to full load torque is Ts/Tn = (Is/In)2sn = x2(Isc/In)2sn
  • Auto-trnasformer startor:
  • The auto-transformer starter is used to reduce the phase voltage to the fraction x of normal value. The starting current is Is = xIsc and starting torque Ts = x2Tsc
  • The ratio of statig torque to full load torque is Ts/Tn = (Is/In)2sn = x2(Isc/In)2sn
  • Star- Delta startor
  • A motor must be built to run normally with a mesh connected stator winding. At starting the winding is connected temporarily in star. The phase voltage is thus reduced to 1/√3 = 0.58 of normal.
  • The starting current per pahse is Is = 0.58Isc, the line current is (0.58)2Isc = 0.33Isc, the starting torque is one third of short circuit value.
  • the ratio to starting torque to full load torque is Ts/Tn = (1/3)(Isc/In)2sn
  • Cogging and Crawling:
  • If the number of stator slots S1 equal to the rotor slots S2, the machine may efuse to start at all, this is called cogging or teeth locking.
  • With other ratios S2/S1, the motor may exhibit a tendency to run stabnly at low speed (one-seventh of normal): this is called crawling.
  • The 5th harmonic r.m.f rotates agaonst the fundamental at one-fifth synchronous speed.
  • The 7th harmonic r.m.f rotates with the fundamental at one-seventh synchronous speed.
  • If the harmonic torques are sufficiently pronounced, the seventh harmonic may prevent the motor speed exceeding abiut one-seventh of normal, since the downward slope of the resultant torque at this speed is a stable running condition over the torque range between the maximum and minimum points. The motor therefore crawls.
  • If n1 is the synchronous speed of fundamental, and n the speed of the rotor, then the synchronous speed of the thirteenth harmonic is +n1/13, or relative to the rotor -(n1-n)/13. The rotor runs at a speed n, and so rotates its own thirteenth harmonic at a speed -(n1-n)/13+n relative to the stator. The sttor and rotor thirteenth harmonic fall into step when +n1/13 = -(n1-n)/13+n i.e. n= (1/7)n1. Thus the torque discontinuity at one seventh synchronous speed is here produced not by the seventh harmonic, but by the thirteen.

Induction Machines-Theory

Induction Machines-Theory

  • The induction motor consists of a fixed core, the stator, carrying a three phase winding in slots on its bore.
  • The stator winding is connected to the supply, and a uniform rotating magnetic filed is produced therein.
  • It works based on principle of Electro-magnetic interaction
  • Speed of the stator m.m.f is synchronous speed
  • The speed of rotation,n, of the rotor is less than the synchronous speed by a fraction,s known as the slip
  • A high ratio of resistance to reactance is desirable under starting conditions, but the resistance should be low for running near synchronous speed, the normal condition
  • The induction motor is a machine of substantially constant speed, and fills the same role as the plain shunt motor among the dc machines
  • The cage rotor is adaptable to any number of poles. whereas the slip-ring winding has to be made for one(or possibly two) definite values of p.
  • leakage flux is greater than transformer in induction machine due to its air gap
  • Power relations:
  • Power input to the stator per phase is P1 = V1I1cosØ1
  • Power delivered by transformer action to the rotor, P2
  • The mechanical power developed at the rotor, Pm = (1-s)P2
  • Rotor power loss is I22r2 = sP2 = s.rotor input
  • P2:Pm:I22r2 = 1:(1-s):s
  • If the rotor had no resistance it could develop no torque
  • condition for maximum torque is r2 = ±sx2
  • Slip values for different operations: If s is positive and between 0 and 1 : Motor, If s is negative and -1 to 0 : generator, If s greater than unity: braking
 




Solved Problems
1.A 220-V, three-phase, two-pole, 50-Hz induction motor is running at a slip of 5 percent. Find:
(a) The speed of the magnetic fields in revolutions per minute
(b) The speed of the rotor in revolutions per minute
(c) The slip speed of the rotor
(d) The rotor frequency in hertz

SOLUTION:

(a) The speed of the magnetic fields is

(b) The speed of the rotor is


(c) The slip speed of the rotor is


(d) The rotor frequency is



2.A three-phase, 60-Hz induction motor runs at 890 r/min at no load and at 840 r/min at full load.
(a) How many poles does this motor have?
(b) What is the slip at rated load?
(c) What is the speed at one-quarter of the rated load?
(d) What is the rotor’s electrical frequency at one-quarter of the rated load?
SOLUTION
(a) This machine has 8 poles, which produces a synchronous speed of

(b) The slip at rated load is


(c) The motor is operating in the linear region of its torque-speed curve, so the slip at ¼ load will be


The resulting speed is


(d) The electrical frequency at ¼ load is

Saturday, April 16, 2011

Transformers- Testing

Transformers- Testing

 
 
    No-load test:
  • As the name suggests, the secondary is kept open circuited and nominal value of the input voltage is applied to the primary winding and the input current and power are measured.
  • This test is performed to determine core or iron loss, Pi and no-load current I0.
  • This test is helpful in determination of magnetizing component Im’ energy component Ie and so no-load resistance R0 being given as V1/Ie and no-load reactance given as V1/Im.

  • In this test secondary (usually high voltage) winding is left open, all metering instruments (ammeter, voltmeter and wattmeter) are connected on primary side and normal rated voltage is applied to the primary (low voltage) winding, as illustrated below





  • Since no load current I0 is very small, therefore, pressure coils of watt meter and the volt meter should be connected such that the current taken by them should not flow through the current taken by them should not flow through the current coil of the watt meter




  • Short Circuit Test:
  • This test is performed to determine the full-load copper loss and equivalent resistance and reactance referred to secondary side.



  • In this test, the terminals of the secondary (usually the low voltage) winding are short – circuited, all meters (ammeter, voltmeter and wattmeter) are connected on primary side and a low voltage, usually 5 to 10 % of normal rated primary voltage at normal frequency is applied to the primary, as shown in fig below. 



  • The applied voltage to the primary, say Vs’ is gradually increased till the ammeter A indicates the full load current of the side in which it is connected. The reading Ws of the wattmeter gives total copper loss (iron losses being negligible due to very low applied voltage resulting in very small flux linking with the core) at full load. Le the ammeter reading be Is.





  • Sumpner’s Test or Back to Back Test
  • This test is mainly performed to determine temperature rise.



  • In this test two transformers are loaded fully, in similar way as two dc machines in a regenerative test, and the power required from the supply is just to meet the iron and full load copper losses of the two transformers.



  • It needs two identical transformers







  • Practice Objectives:

    1. In a single-phase transformer, the magnitude of leakage reactance is twice that of resistance of both primary and secondary. With secondary short-circuited, the input power factor is
    a. 1/2
    b. 1/5
    c. 2/5
    d. 1/3

    2. When short-circuit test on a transformer is performed at 25 V, 50 Hz, the drawn current ‘I1’ is at a lagging p.f. angle of Φ1. If the test is performed at 25 V, 25 Hz and the drawn current “I2’ is at a lagging p.f. angle of Φ2, then
    a. I2 > I1 and Φ2 < Φ1 b. I2 > I1 and Φ2< Φ1 c. I2 < I1 and Φ2 > Φ1
    d. I2 < I1 and Φ2 > Φ1

    3.A 20 kVA, 2000/200 V, 1-phase transformer has nameplate leakage impedance of 8% Voltage required to be applied on the high - voltage side to circulate full - load current with the low voltage winding short-circuited will be
    a. 16 V
    b. 56.56 V
    c. 160 V
    d. 568.68 V

    4. In a 100 kVA, 1100/220 V, 50 Hz single -phase trans former with 2000 turns on the high -voltage side, the open- circuit test result gives 220 V, 91 A, 5kW on low voltage side. The core-loss component of current is, approximately
    a. 9.1 A
    b. 22.7 A
    c. 45.0 A
    d. 91 A

    5. A 1 kVa, 200/100 V, 50 Hz, single-phase transformer gave the following test results on 50 Hz :
    OC (LV side) : 100 V, 20 watts
    SC (HV side) : 5 A, 25 watts
    It is assumed that no-load loss components are equally divided. The above tests were then conducted on the same transformer at 40 Hz.
    Tests results were:
    OC (HV):160 V, W1 watts.
    SC (LV): 10 A, W2 watts
    neglecting skin effect, W1 and W2 will be

    a. W1 = 16 watts, W2 = 25 watts
    b. W1 = 25 watts, W2 = 31.25 watts
    c. W1 = 20 watts, W2 = 20 watts
    d. W1 = 14.4 watts, W2 = 25 watts

    6. Match List I (Test) with List II (Quantities) and select the correct answer using the code given below the lists:
    List I
    A. O C Test
    B. S C Test
    C. Sumpner’s Test
    D. Load Test
    List II
    1. Copper loss and iron loss
    2. Total losses
    3. Iron loss
    4. Copper loss
    Codes;
    ---A B C D
    a. 3 4 1 2
    b. 2 1 4 3
    c. 3 1 4 2
    d. 2 4 1 3


    Solved Problems

    1. A single-phase 10-kVA 480/120-V transformer is to be used as an auto-transformer tying a 600-V distribution line to a 480-V load. When it is tested as a conventional transformer, the following values are measured on the primary (480-V) side of the transformer:
    Open-circuit test Short-circuit test
    VOC = 480 V VSC = 10.0 V
    IOC = 0.41 A ISC = 10.6 A
    VOC = 38 W PSC = 26 W
    Find the per-unit equivalent circuit of this transformer when it is connected in the conventional manner. What is the efficiency of the transformer at rated conditions and unity power factor? What is the voltage regulation at those conditions?

    Solution:
    The base impedance of this transformer referred to the primary side is
    The open circuit test yields the values for the excitation branch (referred to the primary side):

    The excitation branch elements can be expressed in per-unit as


    The short circuit test yields the values for the series impedances (referred to the primary side):

    The resulting per-unit impedances are

    The per-unit equivalent circuit is

    At rated conditions and unity power factor, the input power to this transformer would be PIN = 1.0 pu.
    The core losses (in resistor RC) would be


    The copper losses (in resistor REQ) would be

    The output power of the transformer would be

    and the transformer efficiency would be

    The output voltage of this transformer is


    The voltage regulation of the transformer is




Transformers-parallel operation

Transformers-parallel operation


  • Requirements for parallel operation of transformers:


  • a)the same voltage-ratio
    b)the same per-unit impedance
    c)the same polarity
    d)the same phase sequence and zero relative phase displacement.
    (c) and (d) are absolutely essential, (a) must satisfy to a close degree, in (b), more latitude. it decides load sharing

  • The currents carried by two transformers are proportional to their ratings if their ohmic impedance are inversely proportional to those ratings and their per-unit impedance are identical.

  • A difference in the per-unit impedance results in a divergence of phase angle of the two currents, i.e. two transformers will work at different power factors


  • Transformers can be operated in parallel:


  • Transformer 1: Yy Yd Yd
    Transformer 2: Dd Dy Yz

    Practice Objectives:
    1. If all other requirements for parallel operation of transformer are fulfilled, which one of following pairs of three phase transformers, with given VECTOR GROUPS, can be operated in parallel?
    a. Y d 1 and Yy 0
    b. Y d 1 and Dy 11
    c. Dd 6 and Dy 1
    d. Dd 0 and Dy 11

    2.Two transformers operating in parallel will share the load depending upon their
    a. Ratings
    b. Leakage reactance
    c. Efficiency
    d. Per unit impedance

    3.If per unit impedance of two transformers connected in parallel are not equal, then which one of the following statements is correct?
    a. The power factor of the two transformers will be different from that of the connected load
    b. Transformers will get overloaded
    c. Dead short circuit occurs
    d. The transformer with higher per unit impedance will share more load

    4.Two single phase transformers A and B are connected in parallel, observing all requirements of a parallel operation, except that the induced voltage Ea is slightly greater than Eb; Zea and Zeb being the equivalent impedances of A and B, both referred to the secondary side.



    Under this operating condition with the primary bus-bars being energized, a circulating current will flow:
    a. Only in the secondary windings of A and B
    b. In both the primary and the secondary windings of A and B
    c. In both the primary and the secondary windings of A and B, as well as in the primary side network
    d. In the primary and the secondary windings of A and B, and boost the voltages on the secondary side of both A and B

    Solved Problems
    1. A 500 kVA. transformer with 0.01pu resistance and 0.05 pu reactance is connected in parallel with a 250 kVA transformer with 0.015pu resistance and 0.04 pu reactance. Find how they share a load of 750 kVA, at a power factor 0.8 lagging.
    Solution:
    choose base kVA as 250 kVA.
    Z1 = 0.01+j0.05 = 0.051/78.70 Ω
    and Z2 = 2(0.015+j0.04 = 0.03+j0.08 = 0.085/69.40 Ω.
    Z1+Z2 = 0.04+j0.13 = 0.136/72.90 Ω.

    total load kVA is S = 750/-36.90 kVA;
    S1 = 750/-36.90 . 0.085/69.40 / 0.136/72.90 = 471/-40.40 kVA
    S1 = 471 kVA at power factor 0.762 lagging.

    S2 = 750/-36.90 . 0.051/78.70 / 0.136/72.90 = 281/-31.10 kVA
    S1 = 281 kVA at power factor 0.856 lagging.







    Friday, April 15, 2011

    Auto-transformers


    Auto-Transformers





  • An auto-transformer has windings common to primary and secondary. So that the input and output circuits are electrically connected as one continuous winding per phase.




  • In the common part of the winding, the input and output currents are superposed.




  • The principal application of the auto-transformer is in case where voltage ratio is not great.




  • Applications: Boosters,static balancers and induction motor startors.




  • Adavntages:saving in copper, cores and losses




  • As compared to an ordinary 2-winding transformer of same output, an auto-transformer has higher efficiency but smaller size. Moreover, its voltage regulation is also superior.




  • Weight of copper in auto-transformer=(1-K)×Weight of copper in ordinary 2-winding transformer. Here K=V2/V1




  • Saving is increase when K incrasing unity




  • Inductively transferred power=(1-K)×input




  • Conductively transferred power=K×input




  • Rating of auto transformer = K/(K∼1)× Rating of 2-winding transformer





  • Practice questions:
    1.A single-phase transformer has a rating of 15 k VA, 600/120V. It is reconnected as an auto- transformer to supply at 720 V from a 600 V primary source. The maximum load it can supply is
    a. 90 kVA
    b. 18 kVA
    c. 15 kVA
    d. 12 kVA

    2.An auto-transformer having a transformation ratio of 0.8 supplies a load of 10 kW. The power transferred inductively from the primary to the secondary is
    a. 10kW
    b. 8kW
    c. 2kW
    d. Zero

    3.In case of auto-transformers, which of the following statements are correct?
    1. An auto-transformer requires less copper as compared to a conventional, 2-winding transformer of the same capacity.
    2. An auto-transformer provides isolation between the primary and secondary windings.
    3. An auto-transformer has less leakage reactance as compared to the conventional, 2-winding transformer of the same capacity.
    Select the correct answer using .the codes given below:
    a. 1, 2 and 3
    b. 1 and 2
    c. 1 and 3
    d. 2 and 3

    4.In an auto-transformer of voltage ratio V1 / V2 and V1 > V2, the fraction of power transferred inductively is
    a.V1/(V1+V2 )

    b.V2/V1

    c.(V1-V2)/(V1+V2 )

    d.(V1-V2)/V1

    5.A single-phase, 10 kVA, 2000/200 V, 50 Hz transformer is connected to form an auto transformer as shown in the figure given above. What are the values of V1and I2 respectively?



    a. 2200 V, 55 A
    b. 2200 V, 45 A
    c. 2000 V, 45 A
    d. 1800 V, 45 A

    6. What is the efficiency of an autotransformer in comparison to that of a two winding transformer of the same rating?
    a. Slightly less than that of a two-winding transformer
    b. Same as that of a two-winding transformer
    c. More than that of a two-winding transformer
    d. As low as 1/5th of the efficiency of a two-winding transformer

    7. A two-winding transformer is converted into an auto-transformer. If we apply additive polarity and subtractive polarity for the connections, then the secondary voltage is 2640 V and 2160 V, respectively. What is the ratio of primary to secondary voltage on the original transformer?
    a. 66 : 54
    b. 54 : 66
    c. 10 : 1
    d. 1 : 10

    Solved problems
    1.A 5000-VA 480/120-V conventional transformer is to be used to supply power from a 600-V source to a 120-V load. Consider the transformer to be ideal, and assume that all insulation can handle 600 V.
    (a) Sketch the transformer connection that will do the required job.
    (b) Find the kilovoltampere(kVA) rating of the transformer in the configuration.
    (c) Find the maximum primary and secondary currents under these conditions.
    SOLUTION (a) For this configuration, the common winding must be the smaller of the two windings, and NSE=4NCThe transformer connection is shown below:
    (b) The kVA rating of the auto-transformer can be found from the equation
    (c) The maximum primary current for this configuration will be
    and the maximum secondary current is















    Friday, April 8, 2011

    Transformers_part2



    • Special alloy steel of high resistance and low hysteresis loss is used as transformer core

    • As the flux in the cores is a pulsating one, the magnetic circuit must be lamianted and the separate laminations insulated in order to retain the advantage
      of subdivision

    • Cut the transformer sheets as far as possible along the grain which is the direction in which the material has a higher permeability

    • For large three phase transformer, the core is five-limbed core than , which needs a cross section in the yokes less than that required in usual three limbed core but core losses increase



    • Cross over coils are suitable for currents not exceeding about 20A. They are used for HV windins in comparatively small transformers, and comprise wires of small circular section with double cotton covering

    • Disc coils are made up of a number of flat sections, generally with rectangular wire

    • In Disc coils every turn is contact with oil hence better cooling

    • Sandwich windings , commonly employed for shell-type transformers, allow of easy control over reactance.

    • Conservators are required to take up the expansion and contraction of the oil with changes of temperature in service without allowing the oil to come in contact with air , from which it is liable to take up moisture

    • The displacement of air due to change of oil volume takes place through a breather containing calcium chloride or silica gel, which extracts the moisture from the air.

    • Oil in transfomer serves the double purpose of cooling and insulating.

    • Sludging means slow formation of semi solid hydrocarbons, due to heat and oxidation. It will cause over heating of transformer by blocking the cooling ducts

    • Sludge formation is more in the presence of bright copper surfaces

    • Three phase transformer connections representations:

    • >Group 1: Zero phase displacement--Yy0,Dd0,Dz0
      >group 2: 1800 Phase displacement--Yy6,Dd6,Dz6
      >group 3: 300 lag Phase displacement--Dy1,Yd1,Yz1
      >group 4: 300 lead Phase displacement--Dy11,Yd11,Yz11
    • Star-Star connection is most economical connection for small, high voltages transformers. In this connection third harmonic voltages are absent from the line voltages; unless there is a fourth wire no third harmonic currents will flow. Best suitable for core type construction, for shell type need tertiary winding to stabilize the neutral condition.

    • Delta-Delta connection is an economical connection for large , low voltage transformers.

    • In Delta - Delta, even though one phase faulty the transformer can operate at 58 percent of normal. This connection called Vee(VV) connection.






    Transformers_part1


    • The physical basis of transformer (T/F) is mutual induction between two circuits linked by a common magnetic field. It is a static device.

    • Mutual inductance is the same irrespective of which circuit is primary and which circuit is secondary.

    • The voltage applied to the primary is almost completely concerned in opposing the induced e.m.f.

    • If the primary voltage is constant, the mutual flux remains approximately constant regardless of the load connected across the secondary coil.

    • Important tasks performed by T/F are

    • • Changing voltage and current levels in power system.
      • Matching source and load impedances for maximum power transfer
      • Electrical isolation
    • In core type, to avoid leakage flux, it is usual to have half the primary and half of the secondary winding side-by-side or concentrically on each limb; not primary on one limb and secondary on other limb.




    • The three phase core type, the principle that the sum of the fluxes in each phase in a given direction along the cores is zero.

    • In core type inspection of coils and core is easy.

    • The shell type is more robust mechanically.

    • In shell type core, the cooling is good.

    • The e.m.f induced in transformer given by: E = 4.44fΦmT volts

    • Volt/turn is same in primary winding and secondary winding provided only that it links the same flux in both windings.

    • Both primary and secondary e.m.f.’s are in phase.

    • The e.m.f’s lag by 900 in time on the flux.

    • The applied voltage V1 opposes E1, while E2 provides the secondary output voltage V2.

    • E1/E2 = I2/I1 = T1/T2



    • A small magnetizing current is needed to maintain the magnetic circuit or core in magnetized state, when the secondary is open



    • The m.m.f. of the primary on no load is of the order of 5 per cent of its m.m.f. on full load.

    • The no load current, Io has two components, magnetizing component, Im and loss component, Ir.



    • Leakage between primary and secondary could be eliminated if the winding could be made to occupy the same space.


    • Reductions in leakage flux can achieve by sectionalizing and interleaving the primary and secondary coils.


    • An equivalent circuit is useful for calculations of regulation, efficiency, parallel operation, etc.


    • I2R loss and per-unit reactance voltage in primary and secondary is same.


    • Core loss due to the pulsation of the magnetic flux in the iron producing eddy current and hysteresis loss.

    • I2R loss due to heating of the conductors by the passage of current.

    • Stray loss due to stay magnetic field causing eddy currents in the conductors or in surrounding metal (tank).

    • Dielectric loss in the insulating materials (oil and solid insulation of HT T/F).

    • Efficiency of transformer is given by:


    • Where S is full load kVA, x is per-unit load, Pi is iron loss, Pc is full load copper loss.
    • For maximum efficiency occurs when the variable loss is equal to the constant loss, i.e. x2 Pc= Pi.

    • Maximum efficiency occurs below full load.


    • Maximum efficiency point independent of power factor.

    • The regulation of a transformer refers to the change of secondary terminal voltage between no-load and load conditions: it is usually quoted as a percent value for full load at given power factor.

    • Per unit regulation:

    • Maximum regulation occurs when

    • Zero regulation occurs when
      i.e. leading p.f.

    • On account of the easier insulation facilities, the low-voltage winding is placed nearer to the core in the case of core type and on the outside positions in the case of shell type transformers.

    • Under no-load conditions, the “hum” developed by energized power transformer originates in the core, where the laminations tend to vibrate by magnetic forces.

    • The essential factors in noise production are magnetostriction, mechanical vibrations by the laminations.