Saturday, April 16, 2011

Transformers- Testing

Transformers- Testing

 
 
    No-load test:
  • As the name suggests, the secondary is kept open circuited and nominal value of the input voltage is applied to the primary winding and the input current and power are measured.
  • This test is performed to determine core or iron loss, Pi and no-load current I0.
  • This test is helpful in determination of magnetizing component Im’ energy component Ie and so no-load resistance R0 being given as V1/Ie and no-load reactance given as V1/Im.

  • In this test secondary (usually high voltage) winding is left open, all metering instruments (ammeter, voltmeter and wattmeter) are connected on primary side and normal rated voltage is applied to the primary (low voltage) winding, as illustrated below





  • Since no load current I0 is very small, therefore, pressure coils of watt meter and the volt meter should be connected such that the current taken by them should not flow through the current taken by them should not flow through the current coil of the watt meter




  • Short Circuit Test:
  • This test is performed to determine the full-load copper loss and equivalent resistance and reactance referred to secondary side.



  • In this test, the terminals of the secondary (usually the low voltage) winding are short – circuited, all meters (ammeter, voltmeter and wattmeter) are connected on primary side and a low voltage, usually 5 to 10 % of normal rated primary voltage at normal frequency is applied to the primary, as shown in fig below. 



  • The applied voltage to the primary, say Vs’ is gradually increased till the ammeter A indicates the full load current of the side in which it is connected. The reading Ws of the wattmeter gives total copper loss (iron losses being negligible due to very low applied voltage resulting in very small flux linking with the core) at full load. Le the ammeter reading be Is.





  • Sumpner’s Test or Back to Back Test
  • This test is mainly performed to determine temperature rise.



  • In this test two transformers are loaded fully, in similar way as two dc machines in a regenerative test, and the power required from the supply is just to meet the iron and full load copper losses of the two transformers.



  • It needs two identical transformers







  • Practice Objectives:

    1. In a single-phase transformer, the magnitude of leakage reactance is twice that of resistance of both primary and secondary. With secondary short-circuited, the input power factor is
    a. 1/2
    b. 1/5
    c. 2/5
    d. 1/3

    2. When short-circuit test on a transformer is performed at 25 V, 50 Hz, the drawn current ‘I1’ is at a lagging p.f. angle of Φ1. If the test is performed at 25 V, 25 Hz and the drawn current “I2’ is at a lagging p.f. angle of Φ2, then
    a. I2 > I1 and Φ2 < Φ1 b. I2 > I1 and Φ2< Φ1 c. I2 < I1 and Φ2 > Φ1
    d. I2 < I1 and Φ2 > Φ1

    3.A 20 kVA, 2000/200 V, 1-phase transformer has nameplate leakage impedance of 8% Voltage required to be applied on the high - voltage side to circulate full - load current with the low voltage winding short-circuited will be
    a. 16 V
    b. 56.56 V
    c. 160 V
    d. 568.68 V

    4. In a 100 kVA, 1100/220 V, 50 Hz single -phase trans former with 2000 turns on the high -voltage side, the open- circuit test result gives 220 V, 91 A, 5kW on low voltage side. The core-loss component of current is, approximately
    a. 9.1 A
    b. 22.7 A
    c. 45.0 A
    d. 91 A

    5. A 1 kVa, 200/100 V, 50 Hz, single-phase transformer gave the following test results on 50 Hz :
    OC (LV side) : 100 V, 20 watts
    SC (HV side) : 5 A, 25 watts
    It is assumed that no-load loss components are equally divided. The above tests were then conducted on the same transformer at 40 Hz.
    Tests results were:
    OC (HV):160 V, W1 watts.
    SC (LV): 10 A, W2 watts
    neglecting skin effect, W1 and W2 will be

    a. W1 = 16 watts, W2 = 25 watts
    b. W1 = 25 watts, W2 = 31.25 watts
    c. W1 = 20 watts, W2 = 20 watts
    d. W1 = 14.4 watts, W2 = 25 watts

    6. Match List I (Test) with List II (Quantities) and select the correct answer using the code given below the lists:
    List I
    A. O C Test
    B. S C Test
    C. Sumpner’s Test
    D. Load Test
    List II
    1. Copper loss and iron loss
    2. Total losses
    3. Iron loss
    4. Copper loss
    Codes;
    ---A B C D
    a. 3 4 1 2
    b. 2 1 4 3
    c. 3 1 4 2
    d. 2 4 1 3


    Solved Problems

    1. A single-phase 10-kVA 480/120-V transformer is to be used as an auto-transformer tying a 600-V distribution line to a 480-V load. When it is tested as a conventional transformer, the following values are measured on the primary (480-V) side of the transformer:
    Open-circuit test Short-circuit test
    VOC = 480 V VSC = 10.0 V
    IOC = 0.41 A ISC = 10.6 A
    VOC = 38 W PSC = 26 W
    Find the per-unit equivalent circuit of this transformer when it is connected in the conventional manner. What is the efficiency of the transformer at rated conditions and unity power factor? What is the voltage regulation at those conditions?

    Solution:
    The base impedance of this transformer referred to the primary side is
    The open circuit test yields the values for the excitation branch (referred to the primary side):

    The excitation branch elements can be expressed in per-unit as


    The short circuit test yields the values for the series impedances (referred to the primary side):

    The resulting per-unit impedances are

    The per-unit equivalent circuit is

    At rated conditions and unity power factor, the input power to this transformer would be PIN = 1.0 pu.
    The core losses (in resistor RC) would be


    The copper losses (in resistor REQ) would be

    The output power of the transformer would be

    and the transformer efficiency would be

    The output voltage of this transformer is


    The voltage regulation of the transformer is




3 comments:

  1. Thanks for this great share. This site is a fantastic resource. Keep up the great work here at Sprint Connection! Many thanks.

    Commissioning Services

    ReplyDelete
  2. Electrical transformers have become a part of all modern industries, automation industries, textile industries, refrigeration industries, and all processing industries. In fact, no industry can be imagined without transformers today because every industry has some or the other machinery involved, and no machine can be directly connected to National grid/power supply or work on high tension lines.

    Power Transformers in India | Wire Harness Manufacturer in India

    ReplyDelete